Garage Sub-Panel - 4-Wire FeedI connected a 60 amp sub panel in my garage, I used underground wire rate 600 volts. which has BX cable covered. I have connected the red and black as main power. the blue wire is taped white, connected to the left side of the grounding bar, and bare wire to the right side, I would like to know if this matters with the bare wire to ground, everything seems to be working fine, no breakers are getting warm , and I tripped a breaker to be sure all is working, your help in this matter would be appreciated, Thank you AL. Al, this looks good with one exception. Because this is a sub-panel it requires a 4-wire circuit feed with a dedicated neutral and a dedicated ground, with termination of each going to separate terminals strips or terminal bars. The neutral terminal strip is not connected to the ground at this sub-panel location and is dedicated for neutrals only. The ground wire gets terminated to a separate ground terminal strip that IS connected or bonded to the sub-panel enclosure and is dedicated for ground wires only. The ground wire and neutral wires can be terminated together ONLY at the Main Electrical Panel. |
| Related Articles: Circuit Breakers | |
|
|
Considerations For Zinsco Magnetrip Panels and Circuit Breakers: I have a Magnetrip service entrance box in my house. It does not have a main shut off breaker. Troubleshooting Electrical Outlet Circuit Wiring: In my living room I have 5 outlets. All of them worked fine until tonight. All of a sudden two outlets on one wall quit working. Troubleshooting Home Electrical Circuit Problems Electrical Wiring Connections for Wall Outlets |
