Electrical Question about Electrical Code for Main Service Wires

Electrical Question about Electrical Code for Main Service Wires

 

Electrical Question from Tim about Electrical Code

Received from Tim a Electrician

Question: Can I pull a load circuit (2wires) through the same conduit as the incoming main service wires
example- I need to run a conduit on the outside of the house; the only way to get to the breaker box is to run the conduit to the overhead meter socket then run the wires through the conduit running from the meter socket to the breaker panel in the house with the service wires from the meter socket to the breaker panel

Dave’s Reply:
Thanks for your electrical question.
Hi Tim – NEC Article 230-7 states that the Feeder and Branch circuit conductors are not permitted in the same conduit or raceway with the service conductors.

The Following links will assist you with your electrical question:

For more information about Electrical Code
Electrical Code

This link is helpful as a Electrician
Electrical Code Articles

Make sure not to miss these Resources for: Wiring Diagrams
Wiring Diagrams

Be Careful and Be Safe – Never Work on Energized Circuits!

For Best Results Consult a Licensed Electrical Contractor.
Locate An Electrical Contractor in Your Area


Be Careful and Be Safe - Never Work on Energized Circuits!
Consult your Local Building Department about Permits and Inspections for all projects.
For Best Results Consult a Licensed Electrical Contractor in Your Area

* Please Use This Link to Ask the Electrician a Question using the Question Form. Thank You!

Thanks for Your Comments about this Article or the Website


FOR THE BENEFIT OF ALL:
Questions should be asked from a page of the Same Topic, otherwise your question may be discarded.

*